AP 500

Woodlands Generators

230/400 V - 50 Hz

Generating Set Model

AP 500

Power
Pf. 0,8

Standby kVA

500

Prime kVA

450

Standby:Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046, BS 5514.

Prime:Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,BS 5514. Contact us for the other running periods.Power ratings based on a 40 °C ambient temperature reference.

DESIGN SPECIFICATIONS

  • High quality, reliable and complete power unit
  • Compact design
  • Easy start and maintenance possibility
  • Every generatingset is subjected to a comprehensive test programme which includes full load testing and checking and providing of all control and safety shut down functions testing
  • Full engineered with a wide range of options and accessories: Canopy, soundproof canopy and on mobile units

STANDARD GENSET SPECIFICATIONS

ENGINE:

  • PERKINS heavy duty diesel engine
  • Four cycle, water cooled, turbo charged and after cooled
  • Electronic Governor Control System
  • Direct injection fuel system
  • 24 V D.C. starter and charge alternator
  • Replaceable fuel filters , oil filters and dry element air filters
  • Cooling radiator and fan
  • Starter battery(with lead acid) including Rack and Cables
  • Flexible fuel connection hoses and manual oil sump drain pump
  • Industrial capacity exhaust silencer and steel bellow
  • Jacket water heater (at automatic models)
  • Operation manuals and circuit diagram documents

ALTERNATOR:

  • Brushless,single bearing system,4 poles
  • Insulation class H
  • Standard degree of protection IP21 or IP23
  • Self-exciting and self-regulating
  • Stator winding with 2/3 pitch
  • Impregnation with tropicalised epoxy varnish
  • Solid state Automatic Voltage Regulator

CHASSIS:

  • The complete generating set is mounted as whole on a heavy-duty fabricated, steel base frame. Antivibration pads are fixed between the engine / alternator feet and the base frame.
  • Base frame design incorporates an integral fuel tank.
  • The generating set can be lifted or carefully pushed / pulled by the base frame
  • Dial type fuel gauge and drain bung on the fuel tank
  • Solid state automatic voltage regulator

CANOPY:

  • All canopy parts are designed with modular principles
  • Without welding assembly
  • All metal canopy parts are painted by electrostatic polyester powder paint
  • Exhaust silencer is protected against environment influences
  • Thermally insulated engine exhaust system
  • Emergency stop push button is installed outside of canopy
  • Easy lifting and moving
  • Easy mainteneance and operation

QUALITY STANDARDS:

  • The equipment meets the following standards: ISO 3046, VDE 0530, BS 4999, BS 5000, EN 60034-I, IEC 34. The generating set is manufactured by a full accredited NQA-ISO 9001.

WARRANTY:

  • 12 months warranty from commissioning date as standard.

CONTROL SYSTEM:

  • Control, supervision and protection panel is mounted on the genset base frame.The control panel is equipped as follows;
  • Control Modules Common Features
  • Automatic controls generating set, start and shutdown
  • Front panel programming of the module settings
  • Remote communication via RS 232 port or RS 485 "modbus" output.
  • Scrolling digital LCD display
  • Event logging of shutdown alarms
  • Control Modules Common Features
  • Generator Volts(F-F/F-N)
  • Generator Amperes(L1,L2,L3)
  • Generator Frequency (Hz)
  • Generator kVA
  • Generator kW
  • Generator Cos j
  • Engine Temperature (Cantigrade & Fahrenheit)
  • Engine Speed RPM
  • Engine hours run
  • Plant attery volts
  • XCommon Alarms
  • Under / over generator volts
  • Under / over generator frequency
  • Over current
  • Low oil pressure
  • High engine temperature
  • Under / over speed
  • Low coolantlevel
  • Fail to start
  • Fail to stop
  • Emergency stop
  • Charge fail
  • Low / High battery volts
  • Auto Mains Failure Control System P2020
  • Control with DSE model 5220
  • Static battery charger
  • Emergency stop push button
  • Additional Features
  • Monitoring AC mains supply
  • Provides signal to change over switch gear
  • Easy push button control
  • Stop / Reset-Auto-Manual-Test-Start
  • Additional Metering
  • Mains volts (F-F / F-N)
  • Mains frequency (Hz)
  • Additional Alarms
  • Under / over mains volts
  • Under / over mains frequency
  • Can data fail
  • Can ECU fail
  • Auto Start Control System P2010
  • Control with DSE model 5210 module
  • Emergency stop push button
  • Additional Features
  • Provides signal to load transfer
  • Easy pushbutton control
  • Stop / Reset-Auto-Manual-Test-Start

TECHNICAL DATA

Diesel Generating Sets 230/400 V - 50 Hz

G
R
O
U
P

MODEL

AP 500

Power
Pf. 0,8

500
400

450
360

D
I
E
S
E
L

E
N
G
I
N
E

Engine Make

Perkins

Model

2608C E 16 TAG1

Gross engine power output at rated rpm

kWm
hp

445
596

Aspiration and Cooling

Turbo Charged, After Cooled

Cylinders Capacity

Lt

15.8

Cylinders and Build

6 In line

Engine Speed

rpm

1500

Bore and Stroke

mmxmm

140x171

Compression Ratio

15.8:1

Governor

Electronic

Fuel Consumption

Load
L/hr

1/2

3/4

Full

49.4

71.6

95

Fuel Tank Capacity

Lt

650

Oil Capacity

Lt

68

Water Capacity

Lt

50

Air Intake - Engine

m³/min

34.6

Exhaust Gas Flow

m³/min

75.2

Alternator Voltage Regulation

± %1

OPEN TYPES

Dimensions (length x width x height)

mm

3600x1230x2110

Dry weight

kg

4150

SOUND ATTENUATED TYPE

Canopy Model

AS 710

Dimensions (length x width x height)

mm

5540 x 1660 x 2590

Dry weight

kg

5750

* Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.

OPTIONAL EQUIPMENTS

* Fuel - Water separator filter

* Automatic fuel filling system

* Residential silencer

* Critical silencer

* Trailer

* Low fuel level alarm

* Charge ammeter

* Enclosure,Sound proof canopy

* 4 pole contactor

* Anti condensation heater for alternator

* Main fuel tank

* 3 pole alternator case circuit breaker (only for automatic models)

* Tool kit

* Over sized alternator

* Automatic transfer switch by contactor or motorized circuit breaker

* Engine oil heater