230/400 V - 50 Hz
|
Generating Set Model
|
AP 500
|
|
Power
Pf. 0,8
|
Standby kVA
|
500
|
|
Prime kVA
|
450
|
|
Standby:Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046, BS 5514.
|
|
Prime:Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,BS 5514. Contact us for the other running periods.Power ratings based on a 40 °C ambient temperature reference.
|
|
DESIGN SPECIFICATIONS
- High quality, reliable and complete power unit
- Compact design
- Easy start and maintenance possibility
- Every generatingset is subjected to a comprehensive test programme which includes full load testing and checking and providing of all control and safety shut down functions testing
- Full engineered with a wide range of options and accessories: Canopy, soundproof canopy and on mobile units
|
|
|
|
STANDARD GENSET SPECIFICATIONS
|
|
|
|
ENGINE:
|
- PERKINS heavy duty diesel engine
- Four cycle, water cooled, turbo charged and after cooled
- Electronic Governor Control System
- Direct injection fuel system
- 24 V D.C. starter and charge alternator
- Replaceable fuel filters , oil filters and dry element air filters
- Cooling radiator and fan
- Starter battery(with lead acid) including Rack and Cables
- Flexible fuel connection hoses and manual oil sump drain pump
- Industrial capacity exhaust silencer and steel bellow
- Jacket water heater (at automatic models)
- Operation manuals and circuit diagram documents
|
|
ALTERNATOR:
|
- Brushless,single bearing system,4 poles
- Insulation class H
- Standard degree of protection IP21 or IP23
- Self-exciting and self-regulating
- Stator winding with 2/3 pitch
- Impregnation with tropicalised epoxy varnish
- Solid state Automatic Voltage Regulator
|
|
CHASSIS:
|
- The complete generating set is mounted as whole on a heavy-duty fabricated, steel base frame. Antivibration pads are fixed between the engine / alternator feet and the base frame.
- Base frame design incorporates an integral fuel tank.
- The generating set can be lifted or carefully pushed / pulled by the base frame
- Dial type fuel gauge and drain bung on the fuel tank
- Solid state automatic voltage regulator
|
|
CANOPY:
|
- All canopy parts are designed with modular principles
- Without welding assembly
- All metal canopy parts are painted by electrostatic polyester powder paint
- Exhaust silencer is protected against environment influences
- Thermally insulated engine exhaust system
- Emergency stop push button is installed outside of canopy
- Easy lifting and moving
- Easy mainteneance and operation
|
|
QUALITY STANDARDS:
|
- The equipment meets the following standards: ISO 3046, VDE 0530, BS 4999, BS 5000, EN 60034-I, IEC 34. The generating set is manufactured by a full accredited NQA-ISO 9001.
-
|
|
WARRANTY:
|
- 12 months warranty from commissioning date as standard.
|
|
CONTROL SYSTEM:
|
- Control, supervision and protection panel is mounted on the genset base frame.The control panel is equipped as follows;
- Control Modules Common Features
- Automatic controls generating set, start and shutdown
- Front panel programming of the module settings
- Remote communication via RS 232 port or RS 485 "modbus" output.
- Scrolling digital LCD display
- Event logging of shutdown alarms
- Control Modules Common Features
- Generator Volts(F-F/F-N)
- Generator Amperes(L1,L2,L3)
- Generator Frequency (Hz)
- Generator kVA
- Generator kW
- Generator Cos j
- Engine Temperature (Cantigrade & Fahrenheit)
- Engine Speed RPM
- Engine hours run
- Plant attery volts
- XCommon Alarms
- Under / over generator volts
- Under / over generator frequency
- Over current
- Low oil pressure
- High engine temperature
- Under / over speed
- Low coolantlevel
- Fail to start
- Fail to stop
- Emergency stop
- Charge fail
- Low / High battery volts
- Auto Mains Failure Control System P2020
- Control with DSE model 5220
- Static battery charger
- Emergency stop push button
- Additional Features
- Monitoring AC mains supply
- Provides signal to change over switch gear
- Easy push button control
- Stop / Reset-Auto-Manual-Test-Start
- Additional Metering
- Mains volts (F-F / F-N)
- Mains frequency (Hz)
- Additional Alarms
- Under / over mains volts
- Under / over mains frequency
- Can data fail
- Can ECU fail
- Auto Start Control System P2010
- Control with DSE model 5210 module
- Emergency stop push button
- Additional Features
- Provides signal to load transfer
- Easy pushbutton control
- Stop / Reset-Auto-Manual-Test-Start
|
|
|
|
|
Diesel Generating Sets 230/400 V - 50 Hz
|
|
G
R
O
U
P
|
MODEL
|
AP 500
|
|
Power
Pf. 0,8
|
|
|
500
400
|
|
|
|
450
360
|
|
D
I
E
S
E
L
E
N
G
I
N
E
|
Engine Make
|
Perkins
|
|
Model
|
2608C E 16 TAG1
|
|
Gross engine power output at rated rpm
|
kWm
hp
|
445
596
|
|
Aspiration and Cooling
|
Turbo Charged, After Cooled
|
|
Cylinders Capacity
|
Lt
|
15.8
|
|
Cylinders and Build
|
6 In line
|
|
Engine Speed
|
rpm
|
1500
|
|
Bore and Stroke
|
mmxmm
|
140x171
|
|
Compression Ratio
|
15.8:1
|
|
Governor
|
Electronic
|
|
|
|
|
|
|
Fuel Consumption
|
Load
L/hr
|
|
1/2
|
3/4
|
Full
|
|
49.4
|
71.6
|
95
|
|
|
Fuel Tank Capacity
|
Lt
|
650
|
|
Oil Capacity
|
Lt
|
68
|
|
Water Capacity
|
Lt
|
50
|
|
|
|
|
|
|
Air Intake - Engine
|
m³/min
|
34.6
|
|
Exhaust Gas Flow
|
m³/min
|
75.2
|
|
|
|
|
|
|
Alternator Voltage Regulation
|
± %1
|
|
OPEN TYPES
|
|
Dimensions (length x width x height)
|
mm
|
3600x1230x2110
|
|
Dry weight
|
kg
|
4150
|
|
SOUND ATTENUATED TYPE
|
|
Canopy Model
|
|
AS 710
|
|
Dimensions (length x width x height)
|
mm
|
5540 x 1660 x 2590
|
|
Dry weight
|
kg
|
5750
|
|
|
|
|
|
* Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
|
|
OPTIONAL EQUIPMENTS
|
|
* Fuel - Water separator filter
|
* Automatic fuel filling system
|
|
* Residential silencer
|
* Critical silencer
|
|
* Trailer
|
* Low fuel level alarm
|
|
* Charge ammeter
|
* Enclosure,Sound proof canopy
|
|
* 4 pole contactor
|
* Anti condensation heater for alternator
|
|
* Main fuel tank
|
* 3 pole alternator case circuit breaker (only for automatic models)
|
|
* Tool kit
|
* Over sized alternator
|
|
* Automatic transfer switch by contactor or motorized circuit breaker
|
* Engine oil heater
|
|
|
 |